kVA · kW · amps

Transformer, generator and UPS sizing. Three-phase uses line-to-line volts.

Try an example

Convert from

Unit
Phase
More optionsPower factor 1

75 kVA at 208 V three-phase

How it's calculated
  • Single-phase: amps = kVA × 1,000 ÷ volts.
  • Three-phase: amps = kVA × 1,000 ÷ (√3 × line-to-line volts).
  • kW = kVA × power factor.

Not for motors: motor full-load amps come from the code tables, not this formula.

Worked examples

75 kVA at 208 V three-phase

  • Line current: 208.2 A
  • Real power: 75 kW

100 A at 480 V three-phase

  • Apparent power: 83.14 kVA
  • Real power: 83.14 kW

10 kW at 240 V single-phase

  • Line current: 41.7 A
  • Apparent power: 10 kVA