Transformer fault current

Full-load current and the maximum fault current at a transformer's secondary terminals, from kVA and nameplate impedance.

Try an example

Convert from

More optionsThree-phase
Phase

1,000 kVA, 480 V three-phase, 5.75%Z

How it's calculated
  • Full-load amps = kVA × 1,000 ÷ (√3 × volts).
  • Fault current = full-load amps ÷ (%Z ÷ 100) = 1,202.8 ÷ 0.0575.

Assumes an infinite source (zero utility impedance), so this is the most the transformer can deliver; real fault current is lower. Nameplate %Z has a manufacturing tolerance, and a lower real impedance means more fault current. Not a substitute for a short-circuit study.

Worked examples

1,000 kVA, 480 V three-phase, 5.75%Z

  • Maximum fault current: 20.9 kA
  • Full-load current: 1,202.8 A

75 kVA, 208 V three-phase, 4%Z

  • Maximum fault current: 5.2 kA
  • Full-load current: 208.2 A