Transformer fault current
Full-load current and the maximum fault current at a transformer's secondary terminals, from kVA and nameplate impedance.
Try an example
Convert from
More optionsThree-phase
1,000 kVA, 480 V three-phase, 5.75%Z
How it's calculated
- Full-load amps = kVA × 1,000 ÷ (√3 × volts).
- Fault current = full-load amps ÷ (%Z ÷ 100) = 1,202.8 ÷ 0.0575.
Assumes an infinite source (zero utility impedance), so this is the most the transformer can deliver; real fault current is lower. Nameplate %Z has a manufacturing tolerance, and a lower real impedance means more fault current. Not a substitute for a short-circuit study.
Worked examples
1,000 kVA, 480 V three-phase, 5.75%Z
- Maximum fault current: 20.9 kA
- Full-load current: 1,202.8 A
75 kVA, 208 V three-phase, 4%Z
- Maximum fault current: 5.2 kA
- Full-load current: 208.2 A