Power factor correction

Capacitor kvar needed to raise a load's power factor, and what it does to kVA and current.

Try an example

Convert from

More optionsVolts (for current) 208 V · Three-phase
Phase

100 kW from PF 0.8 to 0.95

Before → after

How it's calculated
  • kvar = kW × (tan φ₁ − tan φ₂), where φ = arccos(power factor).
  • kVA = kW ÷ power factor.

Round up to the next standard capacitor size. Don't correct past unity, and check for harmonic resonance on sites with drives or other non-linear loads.

Worked examples

100 kW from PF 0.8 to 0.95

  • Capacitor needed: 42.1 kvar
  • Apparent power: 125 → 105.3 kVA
  • Line current: 347 → 292.2 A

250 kW from PF 0.72 to 0.95

  • Capacitor needed: 158.8 kvar
  • Apparent power: 347.2 → 263.2 kVA
  • Line current: 963.8 → 730.5 A

40 kW from PF 0.85 to 0.98

  • Capacitor needed: 16.7 kvar
  • Apparent power: 47.1 → 40.8 kVA
  • Line current: 130.6 → 113.3 A