Equipment calculators
Calculators for the machines on a system: motor full-load amps with the wire and protection for a single motor, motor speed and slip, transformer and generator sizing, power factor correction, and the fault current at a transformer and at the end of a feeder.
Motor full-load ampsHorsepower to code-table amps, with the wire and overcurrent protection for a single motor.
Motor speed & slipSynchronous speed from frequency and poles, slip from the nameplate speed, and the same motor on the other frequency.
Transformer sizingPrimary and secondary amps, the next common size, and the overcurrent protection allowed.
Generator & UPS sizingA set is limited by both kW and kVA. Check the load against each, and the largest motor start.
Power factor correctionCapacitor kvar needed to raise a load's power factor, and what it does to kVA and current.
Transformer fault currentFull-load current and the maximum fault current at a transformer's secondary terminals, from kVA and nameplate impedance.
Fault current down a runHow much fault current is left at the end of a feeder, checked against the equipment's interrupting rating.
Quick answers
- Motor full-load amps: 10 hp, 460 V three-phase motor → Full-load current: 14 A
- Motor speed & slip: 4-pole motor at 60 Hz, 1,750 r/min nameplate → Synchronous speed: 1,800 r/min
- Transformer sizing: 75 kVA, 480 V to 208 V three-phase → Primary current: 90.2 A
- Generator & UPS sizing: 100 kW at PF 0.85 → Set size, at least: 150 kVA / 120 kW
- Power factor correction: 100 kW from PF 0.8 to 0.95 → Capacitor needed: 42.1 kvar
- Transformer fault current: 1,000 kVA, 480 V three-phase, 5.75%Z → Worst-case fault current: 23.2 kA
- Fault current down a run: 500 kcmil, 100 ft from 23.2 kA → Fault current at the end: 16.9 kA