AWG / kcmil → mm²
North American wire size to metric area and the matching IEC 60228 size.
Try an example
Convert from
More optionsCopper
12 AWG equals
Metric wire size (IEC)
Area
Weight, bare copper
How it's calculated
- AWG diameter = 0.127 mm × 92^((36 − gauge) ÷ 39), the ASTM B258 definition. 1/0 is gauge 0, 4/0 is gauge −3.
- 1 kcmil = 1,000 circular mils = 0.5067 mm².
- Weight = area × density: copper 8.89 g/cm³, aluminum 2.705 g/cm³. Bare solid metal; stranding adds about 2%, insulation not included.
A match by area isn't a match by ampacity: each code sets its own ratings. “Nearest” can be smaller than the size you started with, so never substitute down.
Worked examples
12 AWG equals
- Cross-section: 3.309 mm²
- Smallest size at least as big: 4 mm²
- Nearest size: 4 mm²
- Thousand circular mils: 6.53 kcmil
- Diameter, solid conductor: 2.053 mm
4/0 AWG equals
- Cross-section: 107.219 mm²
- Smallest size at least as big: 120 mm²
- Nearest size: 120 mm²
- Thousand circular mils: 211.6 kcmil
- Diameter, solid conductor: 11.684 mm
250 kcmil equals
- Cross-section: 126.677 mm²
- Smallest size at least as big: 150 mm²
- Nearest size: 120 mm²
- Thousand circular mils: 250 kcmil
- Pounds per 1,000 ft: 756.7 lb