Transformer sizing

Primary and secondary amps, the next common size, and the overcurrent protection allowed.

Try an example

Convert from

Phase
More optionsNEC
Wiring code

75 kVA, 480 V to 208 V three-phase

Overcurrent protection

How it's calculated
  • Amps = kVA × 1,000 ÷ (√3 × volts).
  • NEC, primary only: 125% from 9 A (next size up), 167% from 2 A, 300% under 2 A. With secondary protection: primary up to 250%, secondary 125%, or 167% under 9 A.

NEC Table 450.3(B), for 600 V or less. Size the primary device to ride through inrush. Secondary conductors have their own tap rules: check them separately.

Worked examples

75 kVA, 480 V to 208 V three-phase

  • Primary current: 90.2 A
  • Secondary current: 208.2 A
  • Next common size: 75 kVA
  • Primary device, primary protection only: 125 A
  • Primary device, with secondary protection: 225 A

30 kVA, 480 V to 208 V three-phase

  • Primary current: 36.1 A
  • Secondary current: 83.3 A
  • Next common size: 30 kVA
  • Primary device, primary protection only: 50 A
  • Primary device, with secondary protection: 90 A

10 kVA, 240 V to 120 V single-phase

  • Primary current: 41.7 A
  • Secondary current: 83.3 A
  • Next common size: 10 kVA
  • Primary device, primary protection only: 60 A
  • Primary device, with secondary protection: 100 A