Lighting layout
How many fixtures a room needs for a target light level, by the lumen method.
Try an example
Convert from
More optionsCoefficient of utilization 0.6 · Light loss factor 0.8 · ft² and foot-candles
2,000 ft² at 50 fc
How it's calculated
- Fixtures = level × area ÷ (lumens × coefficient of utilization × light loss factor), rounded up.
An estimate for an even layout. Coefficient of utilization depends on the room and the fixture: get it from the maker's photometric data. Light loss factor allows for dirt and lamp aging.
Worked examples
2,000 ft² at 50 fc
- Fixtures needed: 42
- Level with that many: 50.4 fc
- In lux: 542.5 lx
- Lighting power: 1,680 W
10,000 ft² at 30 fc
- Fixtures needed: 27
- Level with that many: 31.1 fc
- In lux: 334.8 lx