Transformer fault current

Full-load current and the maximum fault current at a transformer's secondary terminals, from kVA and nameplate impedance.

Try an example

Convert from

More optionsThree-phase
Phase

1,000 kVA, 480 V three-phase, 5.75%Z

How it's calculated
  • Full-load amps = kVA × 1,000 ÷ (√3 × volts).
  • Fault current = full-load amps ÷ (%Z ÷ 100) = 1,202.8 ÷ 0.0575.
  • Worst case = fault current ÷ 0.9 + 4 × motor full-load amps.

Assumes an infinite source (zero utility impedance), so real fault current is usually lower. The worst case takes %Z 10% under the nameplate, the UL 1561 tolerance from 25 kVA up, and adds 4 × motor full-load amps. Not a substitute for a short-circuit study, and the highest current isn't always the worst arc-flash case.

Worked examples

1,000 kVA, 480 V three-phase, 5.75%Z

  • Worst-case fault current: 23.2 kA
  • At nameplate %Z: 20.9 kA
  • Full-load current: 1,202.8 A

75 kVA, 208 V three-phase, 4%Z

  • Worst-case fault current: 5.8 kA
  • At nameplate %Z: 5.2 kA
  • Full-load current: 208.2 A