Conductor ampacity
What a wire can really carry: the code table, derated for heat and bundling, and held to its terminals.
Try an example
Convert from
More optionsCopper · Usual for the size · NEC
12 AWG copper, 90 °C insulation
How it's calculated
- Derated = table value × ambient factor × bundling factor, starting from the insulation rating.
- Usable = the lowest of the derated value, the table value at the terminal rating, and the small-conductor limit.
- Terminals are taken as 60 °C up to 1 AWG and 75 °C above it, unless the equipment is marked otherwise.
- Ampacities from NEC Table 310.16 (2020), which CEC Tables 2 and 4 (2024) match.
For three or fewer conductors the table applies as it stands. The NEC counts current-carrying conductors and the CEC counts all of them. The ambient factors are the NEC's; check CEC Table 5A in Canada.
Worked examples
12 AWG copper, 90 °C insulation
- Usable ampacity: 20 A
- Table value at 90 °C: 30 A
- Ambient factor: × 1.00
- Bundling factor: × 1.00
- After derating: 30 A
6 AWG copper, 90 °C insulation
- Usable ampacity: 54.6 A
- Table value at 90 °C: 75 A
- Ambient factor: × 0.91
- Bundling factor: × 0.80
- After derating: 54.6 A
500 kcmil copper, 75 °C insulation
- Usable ampacity: 380 A
- Carries the load: 0 A
- Table value at 75 °C: 380 A
- Ambient factor: × 1.00
- Bundling factor: × 1.00