Conductor ampacity

What a wire can really carry: the code table, derated for heat and bundling, and held to its terminals.

Try an example

Convert from

Insulation rating
More optionsCopper · Usual for the size · NEC
Conductor metal
Terminal rating
Wiring code

12 AWG copper, 90 °C insulation

How it's calculated
  • Derated = table value × ambient factor × bundling factor, starting from the insulation rating.
  • Usable = the lowest of the derated value, the table value at the terminal rating, and the small-conductor limit.
  • Terminals are taken as 60 °C up to 1 AWG and 75 °C above it, unless the equipment is marked otherwise.
  • Ampacities from NEC Table 310.16 (2020), which CEC Tables 2 and 4 (2024) match.

For three or fewer conductors the table applies as it stands. The NEC counts current-carrying conductors and the CEC counts all of them. The ambient factors are the NEC's; check CEC Table 5A in Canada.

Worked examples

12 AWG copper, 90 °C insulation

  • Usable ampacity: 20 A
  • Table value at 90 °C: 30 A
  • Ambient factor: × 1.00
  • Bundling factor: × 1.00
  • After derating: 30 A

6 AWG copper, 90 °C insulation

  • Usable ampacity: 54.6 A
  • Table value at 90 °C: 75 A
  • Ambient factor: × 0.91
  • Bundling factor: × 0.80
  • After derating: 54.6 A

500 kcmil copper, 75 °C insulation

  • Usable ampacity: 380 A
  • Carries the load: 0 A
  • Table value at 75 °C: 380 A
  • Ambient factor: × 1.00
  • Bundling factor: × 1.00