House service size
The calculated load of a single dwelling and the service it needs, by the NEC optional method or CEC Rule 8-200.
Try an example
Convert from
More optionsCan't run together · Furnace or duct heater
1,500 ft² by the NEC optional method
How it's calculated
- General load: 3 VA/ft², 4,500 VA for the small-appliance and laundry circuits, plus nameplate appliances.
- NEC 220.82 applies to a service of 100 A or more.
A single dwelling on a 240 V service only. Check the result with your inspector: local rules add to these, and this is a load calculation, not a design. The conductor shown is at 75 °C in a raceway.
Worked examples
1,500 ft² by the NEC optional method
- Service size, at least: 110 A
- Calculated load: 25,140 W
- Copper conductor for that size: 2 AWG
- Connected general load: 31,600 W
- General load after demand: 18,640 W
2,400 ft² by the NEC optional method
- Service size, at least: 125 A
- Calculated load: 26,960 W
- Copper conductor for that size: 1 AWG
- Connected general load: 39,900 W
- General load after demand: 21,960 W