Box fill

The box volume your wires and devices need, counted the NEC or the CEC way.

Try an example

Convert from

Wiring code
Internal cable clamps (NEC only)
More optionsin³
Box volume in

Box fill by the NEC

77.78% against Full77.78%Full

What takes up the space

How it's calculated
  • Conductors from NEC Table 314.16(B): 14 AWG 2.00 in³, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00, 6 AWG 5.00.
  • Each switch or receptacle counts as two of the largest conductor, each stud or hickey as one.
  • NEC: all internal clamps count as one. The first four grounding conductors count as one, and each after that as a quarter. Wire connectors don't count.

Count each insulated conductor entering or leaving the box once. Pigtails don't count. The NEC and CEC allow different space per conductor, so a result under one doesn't carry over to the other.

Space per conductor
Wire sizeNEC 314.16(B)CEC Table 22
14 AWG2.00 in³24.6 mL
12 AWG2.25 in³28.7 mL
10 AWG2.50 in³36.9 mL
8 AWG3.00 in³45.1 mL
6 AWG5.00 in³73.7 mL

Worked examples

Box fill by the NEC

  • Fits the box: 77.8%
  • Minimum box volume: 14 in³
  • Box volume: 18 in³
  • Spare: 4 in³
  • 4 × 14 AWG: 8 in³

Box fill by the NEC

  • Too full: 150%
  • Minimum box volume: 27 in³
  • Box volume: 18 in³
  • Short by: 9 in³
  • 6 × 12 AWG: 13.5 in³