Box fill
The box volume your wires and devices need, counted the NEC or the CEC way.
Try an example
Convert from
More optionsin³
Box fill by the NEC
What takes up the space
How it's calculated
- Conductors from NEC Table 314.16(B): 14 AWG 2.00 in³, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00, 6 AWG 5.00.
- Each switch or receptacle counts as two of the largest conductor, each stud or hickey as one.
- NEC: all internal clamps count as one. The first four grounding conductors count as one, and each after that as a quarter. Wire connectors don't count.
Count each insulated conductor entering or leaving the box once. Pigtails don't count. The NEC and CEC allow different space per conductor, so a result under one doesn't carry over to the other.
Space per conductor
| Wire size | NEC 314.16(B) | CEC Table 22 |
|---|---|---|
| 14 AWG | 2.00 in³ | 24.6 mL |
| 12 AWG | 2.25 in³ | 28.7 mL |
| 10 AWG | 2.50 in³ | 36.9 mL |
| 8 AWG | 3.00 in³ | 45.1 mL |
| 6 AWG | 5.00 in³ | 73.7 mL |
Worked examples
Box fill by the NEC
- Fits the box: 77.8%
- Minimum box volume: 14 in³
- Box volume: 18 in³
- Spare: 4 in³
- 4 × 14 AWG: 8 in³
Box fill by the NEC
- Too full: 150%
- Minimum box volume: 27 in³
- Box volume: 18 in³
- Short by: 9 in³
- 6 × 12 AWG: 13.5 in³