Voltage drop
Voltage drop on a run, and the smallest wire that keeps it within your target.
Try an example
Convert from
More optionsAWG / kcmil · Feet · Copper · Steel conduit · Parallel sets 1 · Target drop 3 %
12 AWG copper, 100 ft, 16 A at 120 V single-phase
How it's calculated
- Single-phase: drop = 2 × amps × Z × one-way length ÷ parallel sets.
- Z = √(R² + X²), the most any power factor could give.
- R = 2.0117, X = 0.068 Ω per 1,000 ft, AC at 75 °C.
- R and X from NEC Chapter 9 Tables 8 and 9: stranded, three conductors in one conduit. Past 500 kcmil, reactance sets a floor that a bigger wire can't get under.
NEC informational notes suggest at most 3% for a branch circuit or feeder and 5% overall.
Worked examples
12 AWG copper, 100 ft, 16 A at 120 V single-phase
- Voltage drop: 5.37%
- Drop in volts: 6.44 V
- Voltage at the load: 113.6 V
- Smallest size for this run: 8 AWG
4/0 AWG aluminum, 250 ft, 150 A at 208 V three-phase
- Voltage drop: 3.52%
- Drop in volts: 7.32 V
- Voltage at the load: 200.7 V
- Smallest size for this run: 300 kcmil
10 AWG copper, 150 ft, 20 A at 277 V single-phase
- Voltage drop: 2.69%
- Drop in volts: 7.44 V
- Voltage at the load: 269.6 V
- Smallest size for this run: 10 AWG