Voltage drop

Voltage drop on a run, and the smallest wire that keeps it within your target.

Try an example

Convert from

Phase
More optionsAWG / kcmil · Feet · Copper · Steel conduit · Parallel sets 1 · Target drop 3 %
Wire sizes in
Length in
Conductor metal
Run in

12 AWG copper, 100 ft, 16 A at 120 V single-phase

5.37% against 3% target and 5%5.37%3% target5%
How it's calculated
  • Single-phase: drop = 2 × amps × Z × one-way length ÷ parallel sets.
  • Z = √(R² + X²), the most any power factor could give.
  • R = 2.0117, X = 0.068 Ω per 1,000 ft, AC at 75 °C.
  • R and X from NEC Chapter 9 Tables 8 and 9: stranded, three conductors in one conduit. Past 500 kcmil, reactance sets a floor that a bigger wire can't get under.

NEC informational notes suggest at most 3% for a branch circuit or feeder and 5% overall.

Worked examples

12 AWG copper, 100 ft, 16 A at 120 V single-phase

  • Voltage drop: 5.37%
  • Drop in volts: 6.44 V
  • Voltage at the load: 113.6 V
  • Smallest size for this run: 8 AWG

4/0 AWG aluminum, 250 ft, 150 A at 208 V three-phase

  • Voltage drop: 3.52%
  • Drop in volts: 7.32 V
  • Voltage at the load: 200.7 V
  • Smallest size for this run: 300 kcmil

10 AWG copper, 150 ft, 20 A at 277 V single-phase

  • Voltage drop: 2.69%
  • Drop in volts: 7.44 V
  • Voltage at the load: 269.6 V
  • Smallest size for this run: 10 AWG

Back to top ▲