EV charger circuit

The breaker and wire for a charger, treated as a continuous load at 125%.

Try an example

Convert from

Phase
More optionsCopper
Conductor metal

32 A charger at 240 V single-phase

How it's calculated
  • Breaker = charger amps × 125%, up to the next standard size.
  • Wire has to carry the breaker's rating.

NEC 625.40 and 625.41: chargers are continuous loads, sized at 125% of their rating. A listed load management system can lower the feeder load. Wire is at 60 °C up to 1 AWG, and voltage drop is separate.

Worked examples

32 A charger at 240 V single-phase

  • Breaker, at least: 40 A
  • Wire for that breaker: 8 AWG
  • Charging power: 7.7 kW

48 A charger at 240 V single-phase

  • Breaker, at least: 60 A
  • Wire for that breaker: 4 AWG
  • Charging power: 11.5 kW