EV charger circuit
The breaker and wire for a charger, treated as a continuous load at 125%.
Try an example
Convert from
More optionsCopper
32 A charger at 240 V single-phase
How it's calculated
- Breaker = charger amps × 125%, up to the next standard size.
- Wire has to carry the breaker's rating.
NEC 625.40 and 625.41: chargers are continuous loads, sized at 125% of their rating. A listed load management system can lower the feeder load. Wire is at 60 °C up to 1 AWG, and voltage drop is separate.
Worked examples
32 A charger at 240 V single-phase
- Breaker, at least: 40 A
- Wire for that breaker: 8 AWG
- Charging power: 7.7 kW
48 A charger at 240 V single-phase
- Breaker, at least: 60 A
- Wire for that breaker: 4 AWG
- Charging power: 11.5 kW