Motor full-load amps

Horsepower to code-table amps, with the wire and overcurrent protection for a single motor.

Try an example

Convert from

Horsepower
Phase
More options1.15 or more · NEC
Service factor
Wiring code

10 hp, 460 V three-phase motor

Most protection allowed

How it's calculated
  • Full-load current from NEC Tables 430.248 and 430.250, by motor rating: a 480 V system is the 460 V column.
  • Conductors at 125% of table current; protection up to 250% for an inverse-time breaker, 175% for a time-delay fuse, 300% for a non-time-delay fuse.
  • NEC: between standard sizes, the next size up is allowed.

Up to 50 hp three-phase and 10 hp single-phase, for induction motors at usual speeds. Size overloads from the nameplate, not the table. Low-speed, high-torque and multispeed motors go by the nameplate.

Worked examples

10 hp, 460 V three-phase motor

  • Full-load current: 14 A
  • Conductor ampacity needed: 17.5 A
  • Smallest copper conductor: 14 AWG
  • Inverse-time breaker: 35 A
  • Time-delay fuse: 25 A

5 hp, 208 V three-phase motor

  • Full-load current: 16.7 A
  • Conductor ampacity needed: 20.88 A
  • Smallest copper conductor: 12 AWG
  • Inverse-time breaker: 45 A
  • Time-delay fuse: 30 A

1 hp, 115 V single-phase motor

  • Full-load current: 16 A
  • Conductor ampacity needed: 20 A
  • Smallest copper conductor: 14 AWG
  • Inverse-time breaker: 40 A
  • Time-delay fuse: 30 A