Motor full-load amps
Horsepower to code-table amps, with the wire and overcurrent protection for a single motor.
Try an example
Convert from
More options1.15 or more · NEC
10 hp, 460 V three-phase motor
Most protection allowed
How it's calculated
- Full-load current from NEC Tables 430.248 and 430.250, by motor rating: a 480 V system is the 460 V column.
- Conductors at 125% of table current; protection up to 250% for an inverse-time breaker, 175% for a time-delay fuse, 300% for a non-time-delay fuse.
- NEC: between standard sizes, the next size up is allowed.
Up to 50 hp three-phase and 10 hp single-phase, for induction motors at usual speeds. Size overloads from the nameplate, not the table. Low-speed, high-torque and multispeed motors go by the nameplate.
Worked examples
10 hp, 460 V three-phase motor
- Full-load current: 14 A
- Conductor ampacity needed: 17.5 A
- Smallest copper conductor: 14 AWG
- Inverse-time breaker: 35 A
- Time-delay fuse: 25 A
5 hp, 208 V three-phase motor
- Full-load current: 16.7 A
- Conductor ampacity needed: 20.88 A
- Smallest copper conductor: 12 AWG
- Inverse-time breaker: 45 A
- Time-delay fuse: 30 A
1 hp, 115 V single-phase motor
- Full-load current: 16 A
- Conductor ampacity needed: 20 A
- Smallest copper conductor: 14 AWG
- Inverse-time breaker: 40 A
- Time-delay fuse: 30 A