PV string voltage
A cold morning raises a string's voltage. Check it against the system limit, and size the circuit current.
Try an example
Convert from
More optionsStrings in parallel 1
12 modules at -20 °C
How it's calculated
- Cold Voc = Voc × (1 + coefficient × (lowest temperature − 25 °C)).
- String voltage = cold Voc × modules in series.
- Maximum circuit current = Isc × strings × 125%; conductors carry 125% of that again.
NEC 690.7 and 690.8. Use the coefficient from the module's data sheet, and the record low for your site. Dwellings are limited to 600 V, other buildings usually to 1,000 V.
Worked examples
12 modules at -20 °C
- String voltage when cold: 666.2 V
- Most modules in series: 10
- Module Voc when cold: 55.51 V
- Maximum circuit current: 17.4 A
- Conductor ampacity needed: 21.7 A
18 modules at -10 °C
- String voltage when cold: 975.2 V
- Most modules in series: 18
- Module Voc when cold: 54.18 V
- Maximum circuit current: 17.4 A
- Conductor ampacity needed: 21.7 A