kVA · kW · amps
Transformer, generator and UPS sizing. Three-phase uses line-to-line volts.
Try an example
Convert from
75 kVA at 208 V three-phase
How it's calculated
- Single-phase: amps = kVA × 1,000 ÷ volts.
- Three-phase: amps = kVA × 1,000 ÷ (√3 × line-to-line volts).
- kW = kVA × power factor.
Not for motors: motor full-load amps come from the code tables, not this formula.
Worked examples
75 kVA at 208 V three-phase
- Line current: 208.2 A
100 A at 480 V three-phase
- Apparent power: 83.14 kVA
10 kW at 240 V single-phase, PF 1
- Line current: 41.7 A
- Apparent power: 10 kVA