Fault current down a run

How much fault current is left at the end of a feeder, checked against the equipment's interrupting rating.

Try an example

Convert from

More optionsThree-phase · Copper · Parallel sets 1 · PVC conduit or cable · Feet
Phase
Conductor metal
Run in
Length in

500 kcmil, 100 ft from 23.2 kA

How it's calculated
  • f = k × length × fault current × Z ÷ (parallel sets × volts), with k = √3 three-phase and 2 single-phase.
  • M = 1 ÷ (1 + f). Fault current at the end = fault current at the start × M.
  • Z = √(R² + X²) for the conductor at 20 °C, since a cold conductor lets the most through.

An estimate by the point-to-point method, from the worst-case figure at the start of the run. Motors near the far end add to it. Not a substitute for a short-circuit study.

Worked examples

500 kcmil, 100 ft from 23.2 kA

  • Fault current at the end: 16.9 kA
  • Within the equipment's rating: 5.1 kA
  • Reduction along the run: 27.3%
  • Multiplier M: 0.727

4 AWG, 50 ft from 10 kA

  • Fault current at the end: 4.8 kA
  • Reduction along the run: 52%
  • Multiplier M: 0.48