Line ↔ neutral voltage
Three-phase systems: line-to-neutral = line-to-line ÷ √3. Check a meter reading against the limits for its nominal voltage.
Try an example
Convert from
More optionsWye (star)
208 V line-to-line equals
How it's calculated
- Line-to-neutral = line-to-line ÷ √3 (√3 ≈ 1.732).
120/240 V single-phase doesn't follow the √3 rule: choose it under System. Reading limits apply at the service: equipment further down also loses the voltage drop in its wiring.
Worked examples
208 V line-to-line equals
- Line-to-neutral: 120.1 V
- Standard system: 120/208 V
480 V line-to-line equals
- Line-to-neutral: 277.1 V
- Standard system: 277/480 V
277 V line-to-neutral equals
- Line-to-line: 479.8 V
- Standard system: 277/480 V
120 V line-to-neutral equals
- Meter reading: -6.7%
- Line-to-line: 207.8 V
- Standard system: 120/208 V
240 V centre-tapped delta
- High leg to neutral: 207.8 V
- Other two legs to neutral: 120 V
- Line-to-line: 240 V