Conduit fill
The smallest EMT for a mix of wires, or how full a size would be.
Try an example
Convert from
More optionsOver 24 in
3 × 12 AWG + 4 × 10 AWG + 8 × 8 AWG
How it's calculated
- Fill limit: one conductor 53%, two 31%, three or more 40%, a nipple of 24 in or less 60%.
- Conductor areas from NEC Chapter 9 Table 5, EMT areas from Table 4.
EMT only, up to 500 kcmil. Count every conductor, grounds included. Fill is a limit, not a target: a long pull with bends needs room to spare.
Worked examples
3 × 12 AWG + 4 × 10 AWG + 8 × 8 AWG
- Smallest EMT: 1-1/4" (35)
- Conductor area: 0.4171 in²
- Conductors: 15
4 × 4/0 AWG
- Fits this EMT: 38.6%
- Smallest EMT: 2" (53)
- Conductor area: 1.2948 in²
- Conductors: 4
4 × 500 kcmil
- Smallest EMT: 3" (78)
- Conductor area: 2.7936 in²
- Conductors: 4